Specifications
Overview
The BRE and VRTE Series products are Power Distribution Units (PDU) intended for connection to
a 20 Amp AC Mains circuit. The BRE and VRTE Series PDUs connect to AC Mains power through
an IEC-320 C19 style AC Inlet. These PDUs are rated 125/250 Vac, 50/60 Hz, 16 A and can
optionally be configured with single pole thermal breakers or hydraulic-magnetic circuit breakers
used for supplementary over-current protection of the output receptacles
. The BRE and VRTE
Series PDUs can optionally be configured with a Geist Power Meter that provides local monitoring
and display of Current, Voltage, Wattage, and Power Factor.
Environmental
Temperature
Operating: 10°C (50°F) min 45°C (113°F) max
Storage: -25°C (-13°F) min 65°C (149°F) max
Humidity
Operating: 5% min 95% max (non-condensing)
Storage: 5% min 95% max (non-condensing)
Elevation
Operating: 0 m (0 ft) min 2000 m (6561 ft) max
Storage: 0 m (0 ft) min 15240 m (50000 ft) max
Electrical
See nameplate for unit ratings.
Receptacle Ratings
IEC-320 C13 125/250 Volt, 15 Amp (per Receptacle Bank, North American Units)
IEC-320 C13 125/250 Volt, 10 Amp (per Receptacle Bank, Global Units)
CAUTION: DOUBLE POLE NEUTRAL FUSING CAN BE PRESENT. When single pole thermal breakers
are used, one breaker is provided in the hot conductor path and one breaker is provided in the
neutral conductor path. The PDU should only be serviced by the manufacturer.
Receptacle ratings give nameplate component voltage and current ratings. Receptacle output
voltage will be equal to the voltage of the AC Mains supply used to power the PDU.